Fluke 434 User Manual Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 122
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
Fluke 433/434
Users Manual
9-2
Figure 9-2. Characteristics of a voltage swell
During an Interruption the voltage sinks well below its nominal value. In three phase
systems an interruption begins when the voltage on all phases are below threshold and
ends when one phase is equal to or above the interruption threshold plus hysteresis. The
trigger conditions for interruptions are threshold and hysteresis. Interruptions are
characterized by duration, magnitude and time of occurrence. Figure 9-3 explains this.
duration
time
magnitude
NOMINAL
VOLTAGE
INTERRUPTION-INT-
HYSTERESIS
0 VOLT
THRESHOLD
Figure 9-3. Characteristics of a voltage interruption
Rapid voltage changes are quick transitions of the RMS voltage between two steady-
states. Rapid voltage changes are captured based on steady voltage tolerance, steady time,
minimum step detected, and minimum rate (%/s). Figure 9-4 explains this.
Page view 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 121 122

Comments to this Manuals

No comments