Specifications
Trend Recording21
21-11
Energy
Whr, VAhr, VARhr Ranges:
V1 V10 V100 V1000
0.1 mV/A 000.0 kWhr ...
200.0 GWhr
0.000 MWhr ...
2.000 TWhr
00.00 MWhr ...
20.00 TWhr
000.0 MWhr ...
200.0 TWhr
1 mV/A 00.00 kWhr ...
20.00 GWhr
000.0 kWhr ...
200.0 GWhr
0.000 MWhr ...
2.000 TWhr
00.00 MWhr ...
20.00 TWhr
10 mV/A 0.000 kWhr ...
2.000 GWhr
00.00 kWhr ...
20.00 GWhr
000.0 kWhr ...
200.0 GWhr
0.000 MWhr ...
2.000 TWhr
100 mV/A 000.0 Whr ...
200.0 MWhr
0.000 kWhr ...
2.000 GWhr
00.00 kWhr ...
20.00 GWhr
000.0 kWhr ...
200.0 GWhr
1 V/A 00.00 Whr ...
200.0 kWhr
000.0 Whr ...
200.0 MWhr
0.000 kWhr ...
2.000 GWhr
00.00 kWhr ...
20.00 GWhr
Maximum Integration Time: 9999 hours
Whr, VAHr, Resolution and Accuracy:
Maximum Resolution (lowest range) Accuracy
(excl. Clamp
error)
V1 V10 V100 V1000
0.1 mV/A 100 Whr 1 kWhr 10 kWhr 100 kWhr
1 mV/A 10 Whr 100 Whr 1 kWhr 10 kWhr
10 mV/A 1 Whr 10 Whr 100 Whr 1 kWhr
100 mV/A 0.1 Whr 1 Whr 10 Whr 100 Whr
1 V/A 0.01 Whr 0.1 Whr 1 Whr 10 Whr
± 1.5% of meas
± 10 counts
Note: The Usage scale (in Whrs) starts a factor 10 lower than the equivalent Power scale
(in W). This means that after 6 minutes the Usage number and the Power number are of
the same magnitude.
Trend Recording
General
Item Specification
Resolution 1s, 5s, 30s, 1m, 5m, 15m, 30m, 1h, 3h, 6h
Duration 0.5h, 2.5h, 7.5h, 15h, 30h, 150h, 450h, 900h, 75d, 225d, 450d
Memory 1800 min, max, and avg. points for each reading
Page view 112